FOUNDATION Fieldbus Ethernet Gateway

| article number 1-channel version | 19300-1701 |
| FF interface | H1, Linkmaster |
| transmission rate | 31,25 kBit/s |
| power supply to FF fieldbus | 22 V ... 24 V, max. 300mA (only 1-channel version) |
| controller | Motorola Coldfire |
| flash | 256 kB |
| RAM | 256 kB |
| IP code | IP20 |
| cooling | natural convection, fanless |
| galvanic isolation | yes |
| enclosure | Polyamid |
| dimensions | 115 x 45 x 99 mm |
| RoHs2-conform | yes |
| driver software | Windows XP, Vista, 7, 8, 10, 11 |
| available software | FDT 1.2 (isNet FF DTM) |

| article number 2-channel version | 19300-1801 |
| FF interface | H1, Linkmaster |
| transmission rate | 31,25 kBit/s |
| power supply to FF fieldbus | 22 V ... 24 V, max. 300mA (only 1-channel version) |
| controller | Motorola Coldfire |
| flash | 256 kB |
| RAM | 256 kB |
| IP code | IP20 |
| cooling | natural convection, fanless |
| galvanic isolation | yes |
| enclosure | Polyamid |
| dimensions | 115 x 22.5 x 99 mm |
| RoHs2-conform | yes |
| driver software | Windows XP, Vista, 7, 8, 10, 11 |
| available software | FDT 1.2 (isNet FF DTM) |

| article number 4-channel version | 19300-1901 |
| FF interface | H1, Linkmaster |
| transmission rate | 31,25 kBit/s |
| power supply to FF fieldbus | 22 V ... 24 V, max. 300mA (only 1-channel version) |
| controller | Motorola Coldfire |
| flash | 256 kB |
| RAM | 256 kB |
| IP code | IP20 |
| cooling | natural convection, fanless |
| galvanic isolation | yes |
| enclosure | Polyamid |
| dimensions | 115 x 45 x 99 mm |
| RoHs2-conform | yes |
| driver software | Windows XP, Vista, 7, 8, 10, 11 |
| available software | FDT 1.2 (isNet FF DTM) |


Contact
Request an offer
Support request
Downloads
Description
To access FOUNDATION Fieldbus field devices, the main module isNet Lite can be expanded with a FF linkmaster module. This module is available as 1-channel, 2-channel or 4–channel version. Each channel of the module has its own galvanic isolation.
Furthermore the one channel module version includes a voltage supply for the connected field devices, so that an external supply voltage source and a power conditioner can be omitted. Of course, the connection to externally suppliedFF–network segments is also possible. For the modules a free FDT 1.2–compatible communication DTM is available which allows access to the connected FF field devices in FDT frame applications like Pactware.
